ELC Serial
Refer to these sections for details:
Supported Series
PA10 Series, PB14 Series, PC12 Series, PV28 Series
Website: http://www.eaton.com/
PLC Connection Settings
Parameters | Recommended | Options |
---|---|---|
PLC Type | Cutler-Hammer ELC | |
PLC Interface | RS232 |
|
Baud Rate | 9600 | 19200, 38400, 57600, 115200 |
Data Bits | 7 | 7, 8 |
Parity | Even | None, Odd, Even |
Stop Bits | 1 | 1, 2 |
PLC Station # | 1 | 1 ~ 31 |
OT Link DeviceHub Configuration
To configure DeviceHub for this Cutler-Hammer ELC Serial PLC:
- DeviceHub > Add Device
Type: Cutler-Hammer
Driver: ELC Serial - Enter details specific to your environment and click Add Device.
Device Addresses
Bit/Word | Device Type | Format | Range | Description |
---|---|---|---|---|
B | C_Bit | DDD |
0 ~ 255 |
|
B | M | DDDD | 0 ~ 4095 | |
B | S | DDDD | 0 ~ 1023 | |
B | T_Bit | DDD | 0 ~ 255 | |
B | X | OOO | 0 ~ 255 | |
B | Y | OOO | 0 ~ 255 | |
W | T | DDD | 0 ~ 255 | |
W | D | DDDDD | 0 ~ 11999 | |
W | C_32Bit | DDD | 200 ~ 255 | |
W | C | DDD | 0 ~ 199 |