HPE 1400W Flex Slot Platinum Plus Hot-plug Power Supply
Specification | Value |
Input requirements | |
Rated input voltage |
200 to 240 VAC 240 VDC for China only |
Rated input frequency |
50 Hz to 60 Hz Not applicable to 240 VDC |
Rated input current |
8.0 A at 200 VAC 6.7 A at 240 VAC 6.7 A at 240 VDC for China only |
Maximum rated input power |
1600 W at 200 VAC 1600 W at 240 VAC 1600 W at 240 VDC for China only |
BTUs per hour |
5459 at 200 VAC 5459 at 240 VAC 5459 at 240 VDC for China only |
Power supply output | |
Rated steady-state power |
1400 W at 200 VAC to 240 VAC input 1400 W at 240 VDC input for China only |
Maximum peak power |
1400 W at 200 VAC to 240 VAC input 1400 W at 240 VDC input for China only |