Environmental specifications
Specification | Value |
---|---|
Temperature range1 | — |
Operating | 10°C to 35°C (41°F to 95°F) |
Nonoperating | -30°C to 60°C (-22°F to 140°F) |
Relative humidity (noncondensing) | — |
Operating | 8% to 90%
28°C (82.4°F), maximum wet bulb temperature |
Nonoperating | 5% to 95% 38.7°C (101.7°F), maximum wet bulb temperature |
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 305 m (1.8°F per 1000 ft) to 3050 m (10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). The upper limit and rate of change might be limited by the type and number of options installed.
5°C to 10°C (41°F to 50°F) and 35°C to 40°C (95°F to 104°F) at sea level with an altitude derating of 1.0°C per every 175 m (1.8°F per every 574 ft) above 900 m (2953 ft) to a maximum of 3050 m (10,000 ft)
Redundant fans are required when the ambient temperature reaches 35°C (95°F) to 40°C (104°F).
The approved hardware configurations for this system are listed on the Hewlett Packard Enterprise website (http://www.hpe.com/servers/ASHRAE).