GE Fanuc RX3i Ethernet

Estimated reading time: 2 minutes

Refer to these sections for details:

Supported Series

GE Fanuc RX3i Ethernet

Websitehttp://www.ge.com

PLC Connection Settings

Parameters Recommended Options Notes
PLC Type GE Fanuc RX3i (Ethernet)
PLC Interface Ethernet



Port # 18245

OT Link Platform DeviceHub Configuration

To configure DeviceHub for this GE Fanuc RX3i Ethernet PLC:

  1. DeviceHub > Add Device
    Type: GE Fanuc
    Driver: GE Fanuc RX3i Ethernet

  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

Device Type

Format

Range

Description

B

I

DDDDD

1 ~ 32768

 

B

Q

DDDDD

1 ~ 32768

 

B

M

DDDDD

1 ~ 32768

 

B

G

DDDD

1 ~ 7680

 

B

T

DDDD

1 ~ 1024

 

B

SA

DDD

1 ~ 128

 

B

SB

DDD

1 ~ 128

 

B

SC

DDD

1 ~ 128

 

B

S

DDD

1 ~ 25471

 

W

AI

DDDDD

1 ~ 32640

 

W

AQ

DDDDD

1 ~ 32640

 

W

R

DDDDD