Supported Series

Keyence Nano Ethernet series: KV-L20V, 700, 1000, 3000, 5000, 7500

Websitewww.keyence.com

PLC Connection Settings

Parameters Recommended Options Notes
PLC Type Keyence Nano Series

PLC Interface Ethernet

Port # 8501

PLC Station # 0

OT Link Platform DeviceHub Configuration

To configure DeviceHub for this Keyence Nano PLC:

  1. DeviceHub > Add Device
    Type: Keyence
    Driver: Keyence Nano Ethernet

  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

Device Type

Format

Range

Description

B

MR

DDDDdd

0 ~ 399915

Internal auxiliary relay

B

LR

DDDdd

0 ~ 99915

Latch relay

B

CR

DDDdd

0 ~ 99915

Control relay

B

RLY

DDDdd

0 ~ 99915

Relay

B

B

HHHh

0 ~ 32767

Link relay

B

T_Bit

DDDD

0 ~ 9999

Timer

B

C_Bit

DDDD

0 ~ 9999

Counter

B

DM_Bit

DDDDDdd

0 ~ 6553515

Data memory bit

B

TM_Bit

DDDDdd

0 ~ 999915

Temporary data memory bit

B

CM_Bit

DDDDDdd

0 ~ 6553515

Control memory bit

B

EM_Bit

DDDDDdd

0 ~ 6553515

Data memory

B

FM_Bit

DDDDDdd

0 ~ 6553515

File register bit

B

CTC_Bit

D

0 ~ 7

 

B

ZF_Bit

DDDDDDdd

0 ~ 52428715

File register (SQ)

B

W_Bit

HHHHh

0 ~ 524287

Link register bit

B

VM_Bit

DDDDDdd

0 ~ 6553515

 

B

VB_Bit

HHHHh

0 ~ 63999

 

W

CTC

D

0 ~ 7

 

W

CTH

D

0 ~ 3

 

W

Z

DD

1 ~ 12

 

W

TRM

D

0 ~ 7

 

W

C_Preset

DDDD

0 ~ 9999

Counter preset

W

C_Curr

DDDD

0 ~ 9999

Counter current

W

T_Preset

DDDD

0 ~ 9999

Timer preset

W

T_Curr

DDDD

0 ~ 9999

Timer current

W

C

DDDD

0 ~ 9999

Counter

W

T

DDDD

0 ~ 9999

Timer

W

B_Word

HHH

0 ~ 2047

Link relay

W

RLY_Word

DDD

0 ~ 999

Relay

W

VB

HHH

0 ~ 3999

 

W

ZF

DDDDDD

0 ~ 524287

File register (SQ)

W

CR_Word

DDD

0 ~ 999

Control relay

W

LR_Word

DDD

0 ~ 999

Latch relay

W

MR_Word

DDDD

0 ~ 3999

Internal auxiliary relay

W

FM

DDDDD

0 ~ 65535

File register

W

EM

DDDDD

0 ~ 65535

Data memory

W

CM

DDDDD

0 ~ 65535

Control memory

W

VM

DDDDD

0 ~ 65535

 

W

W

HHHH

0 ~ 32767

Link register

W

TM

DDDD

0 ~ 9999

Temporary data memory

W

DM

DDDDD

0 ~ 65535

Data memory