Mitsubishi Melsec-L(Ascii)

Estimated reading time: 2 minutes

Refer to these sections for details:

Supported Series

Mitsubishi Q series (Q03UDE, Q04UDEH, Q06UDEH, Q10UDEH, Q13UDEH, Q20UDEH, Q26UDEH), Mitsubishi L series(L02, L26-BT), MELSEC-Q/L protocol application to CPU of Ethernet interface or Ethernet module.

Websitehttp://www.mitsubishi-automation.com/

PLC Connection Settings

Parameters Recommended Options Notes
PLC Type Mitsubishi MELSEC-L - ASCII Mode (Ethernet)
PLC Interface Ethernet

Port # 4999 1025 to 4999 or 5010 to 65534
Network # 0 0~255
PLC Station # 255 255
Protocol TCP TCP / UDP MC Protocol

PLC Configuration

The setup shown here is for the Mitsubishi Melsec-L(Ascii) module.

OT Link Platform DeviceHub Configuration

To configure DeviceHub for this Mitsubishi Melsec-L PLC:

  1. DeviceHub > Add Device
    Type: Mitsubishi
    Driver: Mitsubishi Melsec-L(Ascii)

  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

Device Type

Format

Range

Memo

B X HHHH 0 ~ 65536 Input Relay
B Y HHHH 0 ~ 65536 Output Relay
B M DDDDD 0 ~ 65535 Internal Relay
B SM DDDD 0 ~ 2047 Special Relay
B L DDDDD 0 ~ 32237 Latch Relay
B F DDDDD 0 ~ 32237 Annunciator
B V DDDDD 0 ~ 32237 Edge Relay
B B DDDDD 0 ~ 32237 Link Relay
B TS DDDDD 0 ~ 25471 Timer Contact
B TC DDDDD 0 ~ 25471 Timer Coil
B SS DDDDD 0 ~ 25471 Retentive Timer Contact
B SC DDDDD 0 ~ 25471 Retentive Timer Coil
B CS DDDDD 0 ~ 25471 Counter Contact
B CC DDDDD 0 ~ 25471 Counter Coil
B SB DDDDD 0 ~ 32237 Special Link Relay
B S DDDD 0 ~ 8191 Step Relay
B DX DDDD 0 ~ 8191 Direct Input
B DY DDDD 0 ~ 8191 Direct Output
W D DDDD 0 ~ 9999 Data Register
W W DDDD 0 ~ 8191 Link Register
W TN DDDDD 0 ~ 25471 Timer Current Value
W SN DDDD 0 ~ 25471 Retentive Timer Current Value
W CN DDDDD 0 ~ 25471 Counter Current Value
W SD DDDD 0 ~ 2047 Special Register
W R DDDD 0 ~ 9999 File Register
W ZR DDDDDD 0 ~ 999999 File Register
W Z DD 0 ~ 20 Index Register