The standby frame link module in bay X contains configuration data which is inconsistent with the active frame link module

Symptom

The standby frame link module in bay X contains configuration data which is inconsistent with the active frame link module. There is a potential for data loss if this issue is not resolved.

This alert is new in HPE OneView 3.1.

ID: hpris.emRegistry.<version>.EmDataReplicationFault

Severity: Critical

Health Category: Enclosure

Resource URI: /rest/v1/Chassis/1/EnclosureManagerBays/1/

Cause

The shared configuration data between the standby and active frame link modules is not successfully replicated on the standby frame link module. Redundant operations may be compromised.

Action
  1. Reset the standby frame link module in bay X, or remove and reinstall.
    WARNING:

    The active frame link module should not be reset while the standby is in this state.

  2. If the issue persists, replace the standby frame link module.

    For more information, see the frame maintenance and service guide on the Hewlett Packard Enterprise website.