The interconnect in bay X was powered off because the temperature exceeded the critical threshold

Symptom

The interconnect in bay X was powered off because the temperature exceeded the critical threshold.

ID: hpris.emRegistry1.0.InterconnectThermalCritical

Severity: Critical

Resource URI: /rest/v1/Chassis/1/InterconnectBays/1/

Cause

A thermal sensor has exceeded the critical threshold.

Action
  1. Verify that all fan bays are populated with an operational fan.
  2. Remove the interconnect module. For more information, see the frame maintenance and service guide on the Hewlett Packard Enterprise website.
  3. Verify that there is no blockage to the cooling inlets, and then reinstall the interconnect module.
  4. If the issue persists, contact Hewlett Packard Enterprise support. For more information, see "Accessing Hewlett Packard Enterprise support."