Installing the Chassis Intrusion Detection switch option

Prerequisites

Before installing this option, be sure you have the following:

  • The components included with the hardware option kit

  • T-15 Torx screwdriver

Procedure
  1. Power down the server (Power down the server).
  2. Remove all power:
    1. Disconnect each power cord from the power source.
    2. Disconnect each power cord from the server.
  3. Do one of the following:
    1. Extend the server from the rack (Extend the server from the rack).
    2. Remove the server from the rack (Remove the server from the rack).
  4. Remove the access panel (Remove the access panel).
  5. Use a T-15 Torx screwdriver to remove the left DIMM guard from the system board.

    Removing the left DIMM guard

  6. Assemble the connector/cable harness pin openings to the alignment pegs on the DIMM guard.
  7. Install the plastic cover on the DIMM guard.

    Assembling the DIMM guard

  8. Use a T-15 Torx screwdriver to install the DIMM guard, and then connect the cable to the system board.

    Installing the DIMM guard and connecting the cable

  9. Install the access panel (Install the access panel).
  10. Install the server in the rack.
  11. Connect each power cord to the server.
  12. Connect each power cord to the power source.
  13. Power up the server (Power up the server).