Environmental specifications

Specification Value
System inlet temperature (standard operating support1
Operating 10°C to 35°C (50°F to 95°F)
Nonoperating -30°C to 60°C (-22°F to 140°F)
Relative humidity (noncondensing)
Operating

8% to 90%

28°C (82.4°F), maximum wet bulb temperature

Nonoperating

5% to 95%

38.7°C (101.7°F), maximum wet bulb temperature

1

All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 305 m (1.8°F per 1,000 ft) to 3,050 m (10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). The upper limit and rate of change might be limited by the type and number of options installed. Under standard operating support, a fan fault or the ambient temperature exceeding 30°C (86°F) might result in reduced system performance issue.