Environmental specifications

Standard specifications
Specification Value
Temperature range1
Operating

10°C to 35°C (50°F to 95°F)

Nonoperating -30°C to 60°C (-22°F to 140°F)
Relative humidity (noncondensing)
Operating 8% to 90% at 28°C (82.4°F) maximum wet bulb temperature
Non-Operating 5% to 95% at 38.7°C (101.7°F) maximum wet bulb temperature
1

All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 304.8 m (1.8°F per 1,000 ft) to 3,048 m (10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour).

ASHRAE Class A3 specifications
Specification Value
Temperature range1
Operating

5°C to 40°C (41°F to 104°F)

Nonoperating -30°C to 60°C (-22°F to 140°F)

Relative humidity (noncondensing)

Operating 8% to 90% at 28°C (82.4°F) maximum wet bulb temperature
Non-Operating 5% to 95% at 38.7°C (101.7°F) maximum wet bulb temperature
1

All temperature ratings shown are for sea level. Good for 40°C operation up to 1,828 m (6,000 ft) with no altitude de-rating. No restriction on product configurations. Abnormal configurations, allowed for up to 96 hours at one time, no more than 15 days maximum per year. Operation above 40°C (104°F) up to 55°C (131°F), no altitude de-rating, 1,828 m (6,000 ft) limit. Some components could be outside the thermal maximum limits. System must be kept running, processor throttling is allowed. Abnormal conditions allow for operation down to -5°C (23°F).

ASHRAE Class A4 specifications
Specification Value
Temperature range1
Operating

5°C to 45°C (41°F to 113°F)

10°C to 35°C (50°F to 95°F) when GPU is installed2

Nonoperating -30°C to 60°C (-22°F to 140°F)

Relative humidity (noncondensing)

Operating 8% to 90% at 28°C (82.4°F) maximum wet bulb temperature
Non-Operating 5% to 95% at 38.7°C (101.7°F) maximum wet bulb temperature
1

All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 125 m (1.8°F per 410 ft) to 900 m (2,953 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). No restrictions on product configurations except for rotating hard drives. PCI cards must be rated for continuous operation with 60°C cooling air. Not rated for operation over 3,030 m (10,000 ft).

2

Fan failure might reduce performance

Extended Edgeline specifications
Specification Value
Temperature range1
Operating

0°C to 55°C (32°F to 131°F)

Nonoperating -30°C to 60°C (-22°F to 140°F)

Relative humidity (noncondensing)

Operating 8% to 90% at 28°C (82.4°F) maximum wet bulb temperature
Non-Operating 5% to 95% at 38.7°C (101.7°F) maximum wet bulb temperature
1

All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 304.8 m (1.8°F per 1,000 ft) to 3,048 m (10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour).