Environmental specifications-system components support matrix
Environmental specification | Support status | ||||||
---|---|---|---|---|---|---|---|
Base system | Fans | SFF drives | SATA M.2 drives | NVME M.2 drives | PCIe I/O cards | PXIe I/O cards | |
Standard Operating Support | Yes | Yes (with redundancy) | Yes | Yes | Yes | Yes | Yes (up to 38 W)1 |
Extended Ambient 40°C Operating Support (ASHRAE Class A3 Compliant) | Yes | Yes (with redundancy)2 | Yes | Yes | Yes | Yes | Yes (up to 38 W)1 |
Extended Ambient 45°C Operating Support (ASHRAE Class A4 Compliant) | Yes | Yes (with redundancy)2 | Yes (less than 8 W) | Yes | Yes3 | Yes | Yes (up to 38 W)1 |
Extended Edgeline 0°C to 55°C Operating Support | Yes4 | Yes (with redundancy)2 | No | Yes | No | Yes5 | Yes (up to 38 W)1 |
1
Maximum altitude is 2,000 m (800 mbar) (at 25 °C ambient temperature)
2
Upon fan failure, the servers in the system might have reduced performance.
3
M.2 drive might exceed its spec by 2°C to 3°C and have slight throttling.
4
Near 55°C inlet ambient temperature, when the CPU is stressed at 100%, the HPE m510 -16c server might have reduced performance.
5
The PCI card must have inlet spec rated at 65°C or higher, and an air speed of 375 ft/min.