Environmental specifications
Specification | Value |
---|---|
System Inlet Temperature, Standard Operating Support1 | — |
Operating | 10°C to 35°C (50°F to 95°F) |
Non-operating | -30°C to 60°C (-22°F to 140°F) |
Relative humidity (non-condensing) | — |
Operating | Minimum to be the higher (more moisture) of -12°C (10.4°F) dew point or 8% relative humidity Maximum to be 24°C (75.2°F) dew point or 90% relative humidity |
Non-operating | 5 to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet bulb temperature, non-condensing. |
Altitude | — |
Operating | 3050 m (10,000 ft)
This value may be limited by the type and number of options installed. Maximum allowable altitude change rate is 457 m/min (1500 ft/min). |
Non-operating | 9144 m (30,000 ft)
Maximum allowable altitude change rate is 457 m/min (1500 ft/min). |
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 305.0 m (1.8°F per 1000 ft) to 3050 m (10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). The upper limit and rate of change might be limited by the type and number of options installed. System performance during standard operating support may be reduced if operating with a fan fault or above 30°C (86°F).
The approved hardware configurations for this system are listed on the Hewlett Packard Enterprise website.