Environmental specifications

Specification Value
System Inlet Temperature, Standard Operating Support1
Operating 10°C to 35°C (50°F to 95°F)
Non-operating -30°C to 60°C (-22°F to 140°F)
Relative humidity (non-condensing)
Operating

Minimum to be the higher (more moisture) of -12°C (10.4°F) dew point or 8% relative humidity

Maximum to be 24°C (75.2°F) dew point or 90% relative humidity

Non-operating 5 to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet bulb temperature, non-condensing.
Altitude
Operating 3050 m (10,000 ft)

This value may be limited by the type and number of options installed. Maximum allowable altitude change rate is 457 m/min (1500 ft/min).

Non-operating 9144 m (30,000 ft)

Maximum allowable altitude change rate is 457 m/min (1500 ft/min).

1

All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 305.0 m (1.8°F per 1000 ft) to 3050 m (10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). The upper limit and rate of change might be limited by the type and number of options installed. System performance during standard operating support may be reduced if operating with a fan fault or above 30°C (86°F).