System Inlet Temperature, Extended Ambient Operating Support

Specification Value
System Inlet Temperature, Extended Ambient Operating Support

For approved hardware configurations, the supported system inlet range is extended to be 5°C to 10°C (41°F to 50°F) and 35°C to 40°C (95°F to 104°F)

All temperature ratings shown are for sea level with an altitude derating of 1.0 °C per every 175 m (1.8°F per every 574 ft) above 900 m (2953 ft) to a maximum of 3050 m (10,000 ft). 1

For approved hardware configurations, the supported system inlet range is extended to be 40°C to 45°C (104°F to 113°F)

All temperature ratings shown are for sea level with an altitude derating of 1.0 °C per every 125 m (1.8°F per every 410 ft) above 900 m (2953 ft) to a maximum of 3050 m (10,000 ft). 1

1 System performance may be reduced if operating in the extended ambient operating range or with a fan fault.