Space and airflow requirements
Leave a minimum clearance of 63.5 cm (25.0 in) in front of the rack.
Leave a minimum clearance of 76.2 cm (30.0 in) in back of the rack.
Leave a minimum clearance of 121.9 cm (48.0 in) from the back of the rack to the rear of another rack or row of racks.
Compute modules draw cool air in through the front and expel warm air through the rear of the frame. Therefore, the front of the frame must be adequately ventilated to enable ambient room air to enter the frame, and the rear of the frame must be adequately ventilated to enable the warm air to escape from the frame.
Hewlett Packard Enterprise Advanced Series Racks, Hewlett Packard Enterprise Series Racks, and Hewlett Packard Enterprise Standard Series Racks provide proper compute module cooling through flow-through perforations in the front and rear doors that provide 65 percent open area for ventilation.
If the front of the rack is not filled with components, the remaining gaps between the components can cause changes in the airflow, which can adversely affect cooling within the rack. Cover these gaps with blanking panels.