Thermal limitations
To ensure continued safe and reliable equipment operation, install or position the rack in a well-ventilated, climate-controlled environment.
The operating temperature inside the rack is always higher than the room temperature and is dependent on the configuration of equipment in the rack. Check the TMRA for each piece of equipment before installation.
- Do not permit optional equipment to impede airflow around the chassis or to increase the internal rack temperature beyond the maximum allowable limits.
- Do not exceed the manufacturer’s TMRA.
List of options with thermal limitations
Processors
Description | Maximum inlet ambient temperature |
---|---|
Intel® Xeon® Processor E5-2643 v4 1 | 30°C (86°F) |
Intel® Xeon® Processor E5-1680 v3 1 | 23°C (73.4°F) |
If the Intel® Xeon® Processor E5-2643 v4 is installed in a 2U node, and a PCIe NIC card, storage controller, or GPU accelerator is installed in slot 2 of the FlexibleLOM 2U node riser cage assembly (PN 798184-B21), note the maximum inlet ambient temperature for the option installed in slot 2.
Expansion boards installed in slot 2 of the FlexibleLOM 2U node riser cage assembly (PN 798184-B21)
Description | Maximum inlet ambient temperature |
---|---|
Low-profile or single-width PCIe card (such as the P440 Smart Array controller or P840 Smart Array controller) | 20°C (68°F) |
Single-width GPU accelerator (such as the NVIDIA Quadro M4000 or the NVIDIA Quadro K4200) | 21°C (69.8°F) |
Double-width GPU accelerator (such as the NVIDIA Tesla K40 or the AMD FirePro S9150) | 23°C (73.4°F) |
GPU accelerators
Description | Maximum inlet ambient temperature |
---|---|
NVIDIA Quadro K4200 1 | N/A |
NVIDIA Quadro M4000 1 | 30°C (86°F) |
NVIDIA Tesla K40 2 | 30°C (86°F) |
NVIDIA Tesla M40 | 29°C (84.2°F) |
NVIDIA Tesla M60 | 22°C (71.6°F) |
NVIDIA Tesla K80 | 22°C (71.6°F) |
NVIDIA Tesla P40 | 30°C (86°F) if the server node is installed in the HPE Apollo r2200 Chassis
25°C (77°F) if the server node is installed in the HPE Apollo r2600 Chassis or the HPE Apollo r2800 Chassis |
NVIDIA Tesla P100 | 24°C (75.2°F) if the server node is installed in the HPE Apollo r2200 Chassis
20°C (68°F) if the server node is installed in the HPE Apollo r2600 Chassis |
NVIDIA GRID K2 | 30°C (86°F) |
Intel Xeon Phi Coprocessor 5110P 2 | 30°C (86°F) |
AMD FirePro S9150 2 | 30°C (86°F) |
AMD FirePro S7150 | 30°C (86°F) |
If a single-width GPU accelerator is installed in slot 2 of the FlexibleLOM 2U node riser cage assembly (PN 798184-B21), and the Intel® Xeon® Processor E5-2643 v4 is installed in a 2U node, the maximum inlet ambient temperature is 21°C (69.8°F).
If a double-width GPU accelerator is installed in slot 2 of the FlexibleLOM 2U node riser cage assembly (PN 798184-B21), and the Intel® Xeon® Processor E5-2643 v4 is installed in a 2U node, the maximum inlet ambient temperature is 23°C (73.4°F).
DIMMs
Description | Maximum inlet ambient temperature |
---|---|
64 GB, quad-rank x4 PC4-2400T-L | 25°C (77°F) |
128 GB, octal-rank x4 PC4-2400T-L | 29°C (84.2°F) |
Description | Maximum inlet ambient temperature |
---|---|
InfiniBand EDR/EN 100-GB 1-port 840QSFP28 Adapter 12 | 20°C (68°F) if using an optical fiber cable in a 2U node 21°C (69.8°F) if using an optical fiber cable in a 1U node 22°C (71.6°F) if using a copper direct-attach cable in a 2U node 23°C (73.4°F) if using a copper cable in a 1U node |
InfiniBand EDR/EN 100-GB 2-port 840QSFP28 Adapter 12 | 20°C (68°F) if using an optical fiber cable in a 2U node 21°C (69.8°F) if using an optical fiber cable in a 1U node 22°C (71.6°F) if using a copper direct-attach cable in a 2U node 23°C (73.4°F) if using a copper direct-attach cable in a 1U node |
100-GB 1-port OP101 QSFP28 x8 Intel Omni-path architecture Adapter 12 | 21°C (69.8°F) in a 2U node 24°C (75.2°F) in a 1U node |
Ethernet 10/25GB 2-port 640SFP28 Adapter 12 | 16°C (60.8°F) if using an optical fiber cable in a 2U node 20°C (68°F) if using an optical fiber cable in a 1U node 24°C (75.2°F) if using a copper direct-attach cable in a 2U node 24°C (75.2°F) if using a copper direct-attach cable in a 1U node |
Ethernet 10/25GB 2-port 640FLR-SFP28 Adapter 12 | 20°C (68°F) if using an optical fiber cable in a 1U node 24°C (75.2°F) if using a copper direct-attach cable in a 1U node |
If a low-profile or single-width PCIe card is installed in slot 2 of the FlexibleLOM 2U node riser cage assembly (PN 798184-B21), and the Intel® Xeon® Processor E5-2643 v4 is installed in the HPE ProLiant XL190r Gen9 Server Node, the maximum inlet ambient temperature is 20°C (68°F).
The maximum inlet ambient temperature varies depending on the node (1U or 2U) and the type of cable (optical fiber cable or copper direct-attach cable).