GE Fanuc CMM Serial

Estimated reading time: 1 minute

Refer to these sections for details:

Supported Series

GE Fanuc CMM Serial series

Websitehttp://www.ge.com

PLC Connection Settings

Parameters Recommended Options Notes
PLC Type GE Fanuc CMM
PLC Interface RS232 RS232/RS485
Baud Rate 19200 9600, 19200, 38400, 57600, 115200
Data Bits 8 7,8 Must be set to 8
Parity Odd None, Even, Odd
Stop Bits 1 1, 2

PLC Station #

0 0 - 255 Not applicable

OT Link Platform DeviceHub Configuration

To configure DeviceHub for this GE Fanuc CMM Serial PLC:

  1. DeviceHub > Add Device
    Type: GE Fanuc
    Driver: GE Fanuc CMM Serial

  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

Device Type

Format

Range

Description

B

I

DDDDD

1 ~ 10000

Input Relay

B Q DDDDD 1 ~ 10000 Output Relay
B M DDDDD 1 ~ 10000 Auxiliary Relay
B G DDDD 1 ~ 7680
B T DDD 1 ~ 256
B SA DDD 1 ~ 128
B SB DDD 1 ~ 128
B SC DDD 1 ~ 128
B S DDD 1 ~ 128
W AI DDDDD 1 ~ 10000 Analog Input Register
W AQ DDDDD 1 ~ 10000 Analog Output Register
W R DDDDD 1 ~ 32640 Data Register