LS Master-K CPU Direct

Estimated reading time: 3 minutes

Refer to these sections for details:

Supported Series

LS Industrial Systems Master-K CPU Direct series (K80S, K120S, K200S, K300S, K1000S, K7M)

Websitehttp://www.lsis.com/

PLC Connection Settings

Parameters Recommended Options Description
PLC Type LS Master-K CPU Direct
PLC Interface RS232 RS232 or RS485
Baud Rate 38400 9600, 19200, 38400
Data Bits 8 8
Parity None Odd, Even, None
Stop Bits 1 1
PLC Station # 0 0 - 31

OT Link Platform DeviceHub Configuration

To configure DeviceHub for this LS Master-K CPU Direct PLC:

  1. DeviceHub > Add Device
    Type: LS Industrial System
    Driver: LS Master-K CPU Direct

  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

Device Type

Format

Range

Description

B

PW_Bit

DDDdd

0 ~ 25515

I/O Relay (P)

B

KW_Bit

DDDdd

0 ~ 25515

Keep Relay (K)

B

MW_Bit

DDDdd

0 ~ 25515

Auxiliary Relay (M)

B

LW_Bit

DDDdd

0 ~ 25515

Link Relay (L)

B

FW_Bit

DDDdd

0 ~ 25515

Special Relay (F)

B DW_Bit DDDdd 0 ~ 999915
B TX DDD 0 ~ 255
B CX DDD 0 ~ 255
B SX DDDD 0 ~ 9999

W

MW

DDD

0 ~ 255

Word type for M

W

LW

DDD

0 ~ 255

Word type for L

W

FW

DDD

0 ~ 255

Word type for F

W PW DD 0 ~ 63
W KW DD 0 ~ 31

W

TW

DDD

0 ~ 255

Timer Present value

W

CW

DDD

0 ~ 255

Counter Present value

W

DW

DDDD

0 ~ 9999

Data register (D)