Mitsubishi FX5U-Ethernet-Binary
Estimated reading time: 5 minutes
Refer to these sections for details:
Supported Series
Mitsubishi FX5U Ethernet Binary module.
Website: http://www.mitsubishi-automation.com/
PLC Connection Settings
Parameters | Recommended | Options | Notes |
---|---|---|---|
PLC Type | Mitsubishi FX5U - Binary mode (Ethernet) | ||
PLC Interface | Ethernet |
|
|
Port # |
Identical to PLC setting |
Recommend: 4999 |
|
PLC Station # | 255 | ||
Network # | 0 | 0~999 |
PLC Configuration
The setup shown here is for the Mitsubishi FX5U Ethernet Binary module.
Communication Data Code: Binary
- Configure multiple Ethernet port numbers in Mitsubishi GX Works3: Project > Parameter > FX5UCPU > Module Parameter > Ethernet Port > Setting Item > External Device Configuration > Detailed Setting
OT Link Platform DeviceHub Configuration
To configure DeviceHub for this Mitsubishi FX5U PLC:
-
DeviceHub > Add Device
Type: Mitsubishi
Driver: Mitsubishi FX5U-Ethernet-Binary -
Enter details specific to your environment and click Add Device.
Device Addresses
Bit/Word |
Device Type |
Format |
Range |
Description |
---|---|---|---|---|
B |
LCS |
DDDD |
0 ~ 1023 |
Long counter Contact |
B |
LCC |
DDDD |
0 ~ 1023 |
Long counter Coil |
B |
SM |
DDDD |
0 ~ 9999 |
Special Relay |
B |
X |
HHHH |
0 ~ 1023 |
Input Relay |
B |
Y |
HHHH |
0 ~ 1023 |
Output Relay |
B |
M |
DDDDD |
0 ~ 65535 |
Internal Relay |
B |
L |
DDDDD |
0 ~ 32237 |
Latch Relay |
B |
F |
DDDDD |
0 ~ 32767 |
Annunciator |
B |
B |
DDDDD |
0 ~ 32237 |
Link Relay |
B |
TS |
DDDD |
0 ~ 1023 |
Timer Contact |
B |
TC |
DDDD |
0 ~ 1023 |
Timer Coil |
B |
SS |
DDDD |
0 ~ 1023 |
Retentive Timer Contact |
B |
SC |
DDDD |
0 ~ 1023 |
Retentive Timer Coil |
B |
CS |
DDDD |
0 ~ 1023 |
Counter Contact |
B |
CC |
DDDD |
0 ~ 1023 |
Counter Coil |
B |
SB |
DDDDD |
0 ~ 32737 |
Special Link Relay |
B |
S |
DDDD |
0 ~ 4095 |
Step relay |
DW |
LCN |
DDDD |
0 ~ 1023 |
Long counter Current Value |
DW |
LZ |
D |
0 ~ 1 |
Long Index Register |
W |
SD |
DDDDD |
0 ~ 11999 |
Special register |
W |
D |
DDDD |
0 ~ 7999 |
Data Register |
W |
R |
DDDDD |
0 ~ 32767 |
File Register |
W |
W |
DDDDD |
0 ~ 32767 |
Link Register |
W |
TN |
DDDD |
0 ~ 1023 |
Timer Current value |
W |
SN |
DDDD |
0 ~ 1023 |
Retentive Timer Current value |
W |
CN |
DDDD |
0 ~ 1023 |
Counter Current value |
W |
SW |
DDDDD |
0 ~ 32767 |
Special Link Register |
W |
Z |
DD |
0 ~ 19 |
Index Register |